CSS 18M-664-500

Series (Base Building Block)

18M-664-500

Model 1

18M-664-500-4.2

Product Overview

Total Storage [kWh]

2656

Max. Power [kW]

1000

Expansion Options 2

18M-885-500-4.2

Standards

Battery designed and built according to IEC621619, IEC62040, IEC61000, UN38.3 Electrical Standards (Container Installations): SANS 10142-1 Fire Protection: ISO 15779, NFPA 2010, NFPA 855, SANS 10177-2 Inverters (Megarevo / Freedom Won Encore): IEC 61683, NRS 097-2-1, EN 62109-1, EN 62109-2, EN 62477-1, EN 61000-6-2, EN 61000-6-4, Pakistan & India IEC61727, IEC 62116

Warranty 3

10 Year on Battery / 10 Year on Inverters / Back-to-back on Sundry Items

BMS Communication

RS485, CAN

EMS Communication 4

RS485, TCP/IP

Value-Added Features

Deployment

Plug-and-play

Cable Entry

Bottom and side entry (Glanding plate provided)

Monitoring and Control

Freedom Won EMS with 1-Year Cloud Software License for 5 Devices – Online monitoring, data logging, remote control capability, power meter integration and 3rd party PV string inverter control

Fire Detection and Surpression

Fire detection panel (EN 54 approved), smoke detectors, indicator bell and siren; high sensitivity smoke detection air sampler (HSSD)

Inert gas fire suppression for the electrical risk (IG541)

All approved to BS EN 15004 with the design concentration of higher-class A for electrical risk and verified by an approved test report and approval BSI (British Standard Institution)

AC In and AC Out (Termination Box) [A]

1600

Container Specifications

Grade

Grade A

Material

COR-TEN steel – White

Size [m]

1 x 12 and 1 x 6

External Height [mm]

2884

Weight Estimate [kg]

25290 + 11560

Cladding

Fluted Chromadek – White

Insulation

50mm Rock Wool

Flooring

Light grey 3mm polyurethane rubberising

Battery Specifications (per battery building block)

Battery Chemistry

Lithium Iron Phosphate (LiFePO4)

Battery Model

megaTower Plus 6M3T (664kWh)

Nominal Voltage [V]

691

Service Life

>15 yrs (>8 000 cycles) at 80% DoD

Inverter Specifications (per inverter building block)

Inverter Make and Type

Encore HPS Hybrid Inverter

Inverter Model

Nominal Output Voltage [V]

400

Rated Output Power [kW] 5

1000

AC Connection

3W+N+PE

Output Frequency [Hz]

50/60

THDi/THDu [%]

<3 / ≤1 linear; or ≤5 nonlinear

Power Factor

1 lagging~1 leading

Standby Power [W]

<20

Optional PV Components (maximum possible values/quantities stated)

MPPT Charge Controller Specifications

MPPT Mode

Boost MPPT

Max. Number of MPPT Modules 6

20

Max. MPPT Power [kW]

60

Max. PV Power [kW] 

1200

Recommended PV Input Voltage Range [V]

450~650

Max. Number of Charge Controller Cabinets

4

Photovoltaic Combiner Specifications

PV Coupling

DC

Max. Number of PV Strings

4 x 48

Max. PV Input Voltage [V]

1000

Max. Input String ISC [A]

20

Input Fuse [A]

25

Max. Number of Outputs (Breakers)

24

Max. Number of Strings per Output

8

Output Breaker Rated Current [A]

125

Output Cable Terminal [mm²]

50

PV SPD Specification [V]

1200 (Type I + Type II)

Protection

Short-circuit, overload and surge

Ordering Information

Lead Time

6-8 Weeks

Customisation Options 7

Advanced EMS features and additional device licenses available

Notes to the specifications

  1. CSS base models include batteries, inverters, fire detection and suppression systems, and the Freedom Won EMS. PV components such as MPPTs, MPPT cabinets, and PV combiner boxes are sold separately.
  2. If an expansion option is required that is not currently available as a standard model option, please inform Freedom Won of this requirement.
  3. See relevant battery and inverter warranties for further details on warranty guarantees and conditions.
  4. To enable EMS functionality on the load and main supply, RS485 or Modbus TCP compatible 3-phase power meters are required. Additionally, they must have an auxiliary power supply. All third-party devices must also be TCP/IP and Modbus TCP compatible to communicate with the EMS.
  5. Any motors exceeding 7% of the selected HPS inverter’s power rating must be fitted with a VSD. The total connected inductive load without VSD’s may not comprise more than 15% of the HPS inverter’s rated power.
  6. Please refer to the HPS specification sheets for the maximum number of MPPT charge controllers compatible with each HPS inverter model.
  7. Additional EMS features and device license are available upon request, please contact Freedom Won for more information.