megaTower Range

megaTower Plus 6M4T

Model

FWMT-0885-HVPA-07670648

Total Energy Capacity [kWh]

885

Usable Energy, 90% DoD [kWh]

796

Recommended Energy per Cycle, 80% DoD [kWh]

708

Battery Current Capacity [Ah]

320×4

Nominal Voltage [V] 1

691

Max/Min Operating Voltage [V]

767/648

Max./Cont. Discharge Current [A] 2

800/800

Max./Cont. Discharge Power [kW]

605/553

Max./Cont. Charge Current [A] 2

640/384

Max./Cont. Charge Power [kW]

442/265

Total Weight – Including Rack [kg]

5984

Crated Weight [kg]

Frame: 530
Isolation Panel: 98
Busbars: 58
Modules: 284

 

Overall Dimensions – H x W x D [mm] 3

1559x5071x714

Crated Dimensions – H x W x D [mm]

Frame: 780x1700x1740
Isolation Panel: 1046x596x486
Busbars: 120x140x4060
Modules: 422x1320x772

 

Module and Cell Configuration

36 Cells per module in series, 6 modules in series per tower. 4 parallel towers per battery

Module Weight [kg]

234

DC Connection

Busbar in isolator cabinet – installer to connect appropriate cables

DC Connection – Fly Leads (no. per electrode) [mm²]

2 x 95mm² Polybraid Cable

Module Enclosure

Mild Steel – powder coated white, IP54 enclosure rating, rack mounted to suit racks on both walls inside 12m long High Cube shipping containers with centre aisle. Note: Container floor might require reinforcement, container weight limitations apply for transport

Protection

Main bank fuses (1000A), fuses in each module (400A), contactors in each master module. Protection against short circuits, overcurrent, cell under and over voltage and temperature, weak cell detection

Control Interface

CAN Bus, Ethernet/Gateway

Human Interface

RJ45 plug for programming or PC access, On/Off button with indicator light

Remote Monitoring

Real time data logging and remote monitoring over Ethernet. Internet connection required

Service Life 4

Standard Warranty: 10 year (or 8000 cycles) 80% DoD, 0.5C Max Discharge, 0.3C Continuous Discharge, 0.3C Max Charge, Max 25deg. Expected life: >15 yrs (>8000 cycles) at 80% DoD

Battery Standards

Designed and buit according to IEC62619, IEC62040, IEC61000, UN38.3

Notes to the specifications

  1. Voltage suitable for various high DC voltage inverters. Please enquire with Freedom Won for pairing support.
  2. Max current duration 2 min every 10min. 1.5 x Max overload can be handled for 5 seconds. Current limits rated for 10°C to 25°C battery temperature. Derating will apply outside this temperature range.
  3. These dimensions do not include the isolation panel on the side. Power supply and isolation panel dimensions H x W x D [mm] 930x440x370mm. Isolation panel door opens towards the front face of the megaTower. Isolation panel can be mounted either side of the megaTower.
  4. Refer to warranty document for further details.